BP344 · Appendix A.5 · Section 7

Handrail & Grab Bar Requirements
BP344 Philippines (IRR 2024)

Mounting height (700–900mm), diameter (30–40mm), 300mm horizontal extension, 50mm wall clearance, and continuity requirements for handrails and grab bars per the 2024 amended IRR.

BP344 · Appendix A.5 · Section 7

Handrail Provisions

A.5.1Handrail height: 700 mm min, 900 mm max above ramp or stair nosing surface.
A.5.2Horizontal extension: 300 mm beyond top and bottom of ramp. The extension shall be parallel to the floor surface.
A.5.3Handrail diameter: 30 mm (1‑3/16") to 40 mm (1‑37/64"). Graspable profile for continuous grip.
A.5.4Minimum wall clearance: 50 mm. Brackets do not obstruct gripping surface.
A.5.5Handrails shall be continuous, with no sharp edges, and return to the wall or floor at both ends to prevent clothing catch.

Key Dimensions

HANDRAIL — CRITICAL MEASUREMENTS
Height (min)700 mm
Height (max)900 mm
Horizontal Extension300 mm (top & bottom)
Diameter30–40 mm
Wall Clearance (min)50 mm
ProfileGraspable, no sharp edges
ContinuityContinuous, ends returned to wall/floor